DocumentCode
920041
Title
A harmonic distortion control technique applied to six-pulse bridge converters
Author
Phipps, James K. ; Nelson, John P.
Author_Institution
NEI Electr. Power Eng. Inc., Arvada, CA, USA
Volume
29
Issue
3
fYear
1993
Firstpage
616
Lastpage
624
Abstract
A practical design approach for controlling power system harmonics through the use of transformer connections applied to a distributed set of six-pulse bridge power converter type loads in industrial power distribution systems is presented. Some common system problems associated with harmonic distortion from six-pulse type converters are defined. A method for reducing harmonic distortion through the use of transformer bank connections to allow for harmonic cancellation is presented
Keywords
distribution networks; electric distortion; load (electric); power convertors; power system harmonics; cancellation; distortion control; distribution systems; industries; loads; power system harmonics; six-pulse bridge power converter; transformer bank; Bridge circuits; Harmonic distortion; Industrial power systems; Petroleum; Power capacitors; Power factor correction; Power harmonic filters; Power system harmonics; Power system planning; Voltage;
fLanguage
English
Journal_Title
Industry Applications, IEEE Transactions on
Publisher
ieee
ISSN
0093-9994
Type
jour
DOI
10.1109/28.222434
Filename
222434
Link To Document