DocumentCode :
926375
Title :
Two-stage current transformers in differential calibration circuits
Author :
Betts, P.J.
Author_Institution :
Commonwealth Scientific and Industrial Research Organisation (CSIRO), National Measurement Laboratory, Division of Applied Physics, Sydney, Australia
Volume :
130
Issue :
6
fYear :
1983
fDate :
1/1/1983 12:00:00 AM
Firstpage :
324
Lastpage :
328
Abstract :
The errors of a 2-stage current transformer (CT) are analysed when used as an isolated device or when used in a differential circuit. It is shown that when the CT is used in a differential circuit, or is operated at near zero external burden, a reduction in the errors of around two orders of magnitude can be gained. It is also shown that where the errors of a CT are largely a result of dielectric leakage, or of partial magnetic coupling, 2-staging will do little or nothing to reduce the errors.
Keywords :
calibration; current transformers; measurement errors; 2-stage current transformer; dielectric leakage; differential calibration circuits; isolated device; measurement errors; partial magnetic coupling;
fLanguage :
English
Journal_Title :
Physical Science, Measurement and Instrumentation, Management and Education - Reviews, IEE Proceedings A
Publisher :
iet
ISSN :
0143-702X
Type :
jour
DOI :
10.1049/ip-a-1.1983.0058
Filename :
4645864
Link To Document :
بازگشت