• DocumentCode
    927668
  • Title

    Transient response of the modified variable-phase-shift automatic voltage regulator

  • Author

    Allos, J.E. ; Mahmood, M.K. ; Al-Qirimli, F.A.M.

  • Author_Institution
    University of Baghdad, Department of Electrical Engineering, College of Engineering, Baghdad, Iraq
  • Volume
    131
  • Issue
    1
  • fYear
    1984
  • fDate
    2/1/1984 12:00:00 AM
  • Firstpage
    10
  • Lastpage
    16
  • Abstract
    In the variable-phase-shift automatic voltage regulator, the output is sampled at half-cycle intervals, and compared to a reference. The error is applied to a phase control circuit and filter, whose output is a sinusoid of constant amplitude, at mains frequency, but variable phase. This is amplified by a class B power amplifier, and added to the mains line voltage in such a sense as to correct it. Theoretical, simulation and experimental results are given to demonstrate the high accuracy (of the order of 0.2%), very fast response (between one half and one cycle) and low distortion of the device.
  • Keywords
    transient response; voltage regulators; class-B power amplifier; constant amplitude sinusoid; filter; half-cycle intervals; mains frequency; mains line voltage; output sampling; phase control circuit; transient response; variable-phase-shift automatic voltage regulator;
  • fLanguage
    English
  • Journal_Title
    Electronic Circuits and Systems, IEE Proceedings G
  • Publisher
    iet
  • ISSN
    0143-7089
  • Type

    jour

  • DOI
    10.1049/ip-g-1:19840003
  • Filename
    4646002