• DocumentCode
    934561
  • Title

    Overcoming problems associated with impedance measurement in pole slipping protection for Dinorwig

  • Author

    Goody, J.L.H.

  • Author_Institution
    CEGB, Design Department, Transmission and Technical Services Division, Guildford, UK
  • Volume
    133
  • Issue
    1
  • fYear
    1986
  • fDate
    1/1/1986 12:00:00 AM
  • Firstpage
    44
  • Lastpage
    48
  • Abstract
    The paper is a follow-up to the paper written by Stalewski, Goody and Downes for the Second IEE International Conference on Developments in Power System Protection in 1980. The paper discusses the required performance of two types of pole-slipping relay which utilise the principle of impedance measurement and explains the difficulties with this method of measurement, as revealed by model machine and system tests, in distinguishing between pole-slipping and certain types of fault conditions. It describes the logic criteria developed for each relay to overcome these problems. The paper also describes the principles involved for the relay installation at Dinorwig, in determining how far each relay should reach in order to detect remote pole-slips.
  • Keywords
    electric impedance measurement; electrical faults; power system protection; pumped-storage power stations; relay protection; earth faults; impedance measurement; pole slipping protection; pole-slipping relay; pumped storage hydroelectric power station;
  • fLanguage
    English
  • Journal_Title
    Generation, Transmission and Distribution, IEE Proceedings C
  • Publisher
    iet
  • ISSN
    0143-7046
  • Type

    jour

  • DOI
    10.1049/ip-c.1986.0007
  • Filename
    4646714