Title :
Transients during 138-kV SF6 breaker switching of low inductive currents
Author :
Elkins, Douglas L. ; Jain, Avi C. ; McDermott, Thomas E. ; Rees, Volker
Author_Institution :
Esso Eng. Ltd., Leatherhead, UK
Abstract :
The authors discusses the effects of switching low inductive currents with 138 kV SF6 breakers in a petrochemical plant. Switching transients are believed to have contributed to the failure of a 13.8 kV PT and a 13.8 kV air magnetic circuit breaker. The high-frequency transient surge can transfer across a transformer due to transformer capacitances between the high- and low-voltage windings. The electromagnetic transient program system (ETPS) model and different case studies are discussed with the effect of different transformer winding capacitances. The interruption mechanism of low inductive currents is also described. This analysis demonstrates the need to conduct switching transient studies and the need for surge arresters on transformer secondary terminals under certain system conditions
Keywords :
circuit breakers; digital simulation; gaseous insulation; petroleum industry; power system analysis computing; power system protection; power transformers; sulphur compounds; surge protection; transformer protection; transformer windings; transients; 138 kV; EMTP; HF; SF6; capacitances; circuit breakers; electromagnetic transient program; interruption mechanism; low inductive currents; petrochemical plant; power systems; power transformers; surge arresters; switching; transformer; transformer protection; transients; windings; Capacitance; EMTP; Electromagnetic modeling; Electromagnetic transients; Magnetic circuits; Magnetic switching; Petrochemicals; Sulfur hexafluoride; Surges; Switching circuits;
Journal_Title :
Industry Applications, IEEE Transactions on