DocumentCode :
934979
Title :
Ineffectiveness of transmission line transpositions at harmonic frequencies
Author :
Arrillaga, J. ; Acha, E. ; Densem, T.J. ; Bodger, P.S.
Author_Institution :
University of Canterbury, Department of Electrical & Electronic Engineering, Christchurch, New Zealand
Volume :
133
Issue :
2
fYear :
1986
fDate :
3/1/1986 12:00:00 AM
Firstpage :
99
Abstract :
There is practically no information on the behaviour of transmission line transpositions at harmonic frequencies. The paper describes a computer model for the calculation of the phase voltages appearing at the end of a multiconductor transmission line. The program can model the effect of transpositions under harmonic voltage or current excitation and variable loading. The effectiveness of the transpositions is shown to deteriorate substantially with increasing frequencies for electrical distances above one-eighth of their respective wavelengths and when the power transmitted is below the natural loading of the line.
Keywords :
harmonics; power transmission lines; computer model; harmonic current excitation; harmonic frequencies; harmonic voltage excitation; multiconductor transmission line; phase voltages; transmission line transpositions; variable loading;