Title
New algorithm of calculating current and voltage phasors for fast protection
Author
Wiszniewski, A.
Author_Institution
Technical University of Wroclaw, Institute of Power Systems, Wroclaw, Poland
Volume
134
Issue
1
fYear
1987
fDate
1/1/1987 12:00:00 AM
Firstpage
81
Lastpage
82
Abstract
Correlation of the distorted signal with sine and cosine functions is one of the best ways of calculating power-frequency phasors. However, if the data window becomes shorter than one cycle, DC transient components introduce large errors. The presented algorithm removes this weakness. It splits the signal into two parts mutually shifted in phase, and correlates both of them with the sinusoidal function only. Comparing the characteristics obtained in the time domain and in the frequency domain, it becomes evident that the new method is superior to the standard one.
Keywords
frequency-domain analysis; power system protection; time-domain analysis; DC transient components; algorithm; cosine functions; current phasors; data window; distorted signal; fast protection; frequency domain; power system protection; power-frequency phasors; sine functions; time domain; voltage phasors;