DocumentCode :
943833
Title :
Double impulse tests of long airgaps. Part 1: Engineering problems and physical processes: the basis of recent tests
Volume :
133
Issue :
7
fYear :
1986
fDate :
10/1/1986 12:00:00 AM
Firstpage :
395
Lastpage :
409
Abstract :
Collaborative tests have been performed using nonstandard impulses, and employing a wide range of diagnostic techniques. Part 1 of the paper describes the need for such tests, the experimental arrangement and the digital data techniques developed for the tests. Part 2 is an account of the decay of the leader channel in long airgaps and the recovery of dielectric strength. It was found that the leader conductivity had a lifetime of the order of 1 ms. In part 3 of the paper, the influence of a nonstandard impulse front on the leader growth is examined in detail. The results show that overstressing of the gap can result in a reduced probability of break-down, and the cause of this effect is studied. In phase-to-phase structures, on the other hand, the case of a negative surge preceding a positive can be particularly dangerous: the effect of pre-existing negative space charges on positive leader growth is therefore described in part 4. Large-scale influences which cause more vigorous leader processes have been observed.
Keywords :
high-voltage techniques; impulse testing; overvoltage; spark gaps; surges; airgaps; digital acquisition; digital data techniques; double impulse tests; gas discharge; high-voltage technology; nonstandard impulses; phase-to-phase insulations; plasma physics; surges; voltage stresses;
fLanguage :
English
Journal_Title :
Physical Science, Measurement and Instrumentation, Management and Education - Reviews, IEE Proceedings A
Publisher :
iet
ISSN :
0143-702X
Type :
jour
DOI :
10.1049/ip-a-1:19860063
Filename :
4647840
Link To Document :
بازگشت