DocumentCode :
943909
Title :
Switching-impulse strength of the external insulation of three-phase power transformers
Author :
Studinger, H. ; Weck, K.-H.
Author_Institution :
Forschungs Gemeinschaft f¿¿r Hochspannungs und Hochstromtechnik EV, Mannheim, West Germany
Volume :
133
Issue :
8
fYear :
1986
fDate :
11/1/1986 12:00:00 AM
Firstpage :
534
Lastpage :
542
Abstract :
The switching-impulse strength phase-to-phase and phase-to-earth has been investigated on a power transformer dummy to provide data for the design of its external clearances. The dummy was equipped with 420 kV bushings, but also simulations were used to obtain smaller or larger distances to earth. The clearances were varied between 2 m and 6 m. The influence of rain is included. The report offers design curves for power transformer clearances covering the range of rated switching-impulse withstand voltages up to 1550 kV, phase-to-earth, and up 2400 kV, phase-to-phase.
Keywords :
electric strength; high-voltage techniques; insulation testing; power transformers; transformer testing; 1550 kV; 2 m to 6 m clearance; 2 to 6 m; 2400 kV; 420 kV; 420 kV bushings; design; external clearances; rain; three-phase power transformers; up 2400 kV; up to 1550 kV;
fLanguage :
English
Journal_Title :
Physical Science, Measurement and Instrumentation, Management and Education - Reviews, IEE Proceedings A
Publisher :
iet
ISSN :
0143-702X
Type :
jour
DOI :
10.1049/ip-a-1.1986.0071