DocumentCode :
943936
Title :
Breakdown characteristics of insulator strings stressed by short tail waves
Author :
Gary, C. ; Garabedian, R. ; Zhang, Z. ; Cristescu, D. ; Enache, R.
Author_Institution :
¿¿lectricit¿¿ de France, Clamart, France
Volume :
133
Issue :
8
fYear :
1986
fDate :
11/1/1986 12:00:00 AM
Firstpage :
552
Lastpage :
561
Abstract :
Traditionally, the withstand voltage of an insulator string to lightning impacts is checked using the standard impulse 1.2/50 ¿¿s. First, the authors show that when a lightning stroke hits the tower or a ground wire, the resulting overvoltages are characterised by much shorter tail durations than the tail of incident lightning currents. The analysis of wave shapes, in particular tail durations of the overvoltages affecting the insulator strings, is carried out in the form of a detailed parametric study. Secondly, the authors describe the routine tests carried out in a HV laboratory to evaluate the withstand voltage of various insulator strings as a function of tail duration of the applied impulses. Five strings of different lengths were tested, with impulse tail durations between 50 ¿¿s and 4 ¿¿s. In conclusion, it clearly appears, when considering the mechanisms resulting in back flashover, that the withstand voltage of insulator strings is much higher than their conventional value for the 1.2/50 ¿¿s impulse.
Keywords :
electric breakdown; high-voltage techniques; insulators; lightning protection; overvoltage protection; power overhead lines; 4 to 50 mus; HV laboratory; back flashover; insulator strings; overvoltages; power overhead lines; routine tests; short tail waves; tail durations; wave shapes; withstand voltage;
fLanguage :
English
Journal_Title :
Physical Science, Measurement and Instrumentation, Management and Education - Reviews, IEE Proceedings A
Publisher :
iet
ISSN :
0143-702X
Type :
jour
DOI :
10.1049/ip-a-1.1986.0074
Filename :
4647852
Link To Document :
بازگشت