• DocumentCode
    946964
  • Title

    Prebreakdown emission current measurements in a 24 kV vacuum interrupter with butt contacts

  • Author

    Vries, L.M.J. ; Damstra, G.C.

  • Author_Institution
    Div. of Res. & Dev., KEMA, Arnhem, Netherlands
  • Volume
    23
  • Issue
    1
  • fYear
    1988
  • fDate
    2/1/1988 12:00:00 AM
  • Firstpage
    97
  • Lastpage
    100
  • Abstract
    Commercial 24-kV vacuum interrupters with butt contacts were tested under DC conditions with three different contact materials: OFHC-copper, stainless steel 304 and Cu/Cr (75/25, wt.%). The critical breakdown field was computed at contact distances of 1, 2 and 3 mm, based on the prebreakdown emission current and the breakdown voltage. While the values for the critical breakdown field for OFHC-copper and stainless steel 304 were in agreement with the values found by other authors, no previous data were found for Cu/Cr.
  • Keywords
    circuit breakers; electric breakdown; switchgear testing; vacuum apparatus; 1 mm; 2 mm; 24 kV; 3 mm; Cu; CuCr; DC conditions; breakdown voltage; butt contacts; contact distances; contact materials; critical breakdown field; prebreakdown emission current; stainless steel 304; testing; vacuum interrupter; Breakdown voltage; Chromium; Circuit testing; Current measurement; Electric breakdown; Interrupters; Resistors; Steel; Vacuum breakdown; Voltage measurement;
  • fLanguage
    English
  • Journal_Title
    Electrical Insulation, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9367
  • Type

    jour

  • DOI
    10.1109/14.2340
  • Filename
    2340