DocumentCode :
949512
Title :
Transient transformer overload ratings and protection
Author :
Weekes, Tony ; Molinski, Tom ; Swift, Glenn
Author_Institution :
Manitoba Hydro, Winnipeg, Man., Canada
Volume :
20
Issue :
2
fYear :
2004
Firstpage :
32
Lastpage :
35
Abstract :
In this paper, standard loss of insulation life equations have been applied to step up transformers as part of the design of an intelligent relay that would calculate the time left before a possible trip (assuming that conditions remained constant) and should allow the operators to avoid tripping the transformer. The basic idea is that the transformer can withstand temperature in inverse proportion to time. The algorithm to derive the hot-spot temperature, the relationship of the hot-spot temperature to probe temperature, as well as the ability to provide operating guidelines for a derated transformer are shown. Revised transformer overload ratings as well as predictive protection can be obtained with an accurate thermal model of the limiting hottest spot temperatures. Based on the constant feedback from actual probe measurements, the thermal model is developed is detailed enough to consistently obtain very accurate results for various loads and seasons.
Keywords :
power transformer insulation; power transformer protection; transients; derated transformer; hot-spot temperature; insulation life loss equations; intelligent relay; operating guidelines; overload protection; predictive protection; probe measurements; probe temperature; step up transformers; thermal model; transient transformer overload ratings; Equations; Feedback; Guidelines; Insulation life; Power transformer insulation; Predictive models; Probes; Protection; Protective relaying; Temperature;
fLanguage :
English
Journal_Title :
Electrical Insulation Magazine, IEEE
Publisher :
ieee
ISSN :
0883-7554
Type :
jour
DOI :
10.1109/MEI.2004.1283260
Filename :
1283260
Link To Document :