Verification of limiter performance in modern excitation control systems
Author :
Girgis, George K. ; Vu, Hoa D.
Author_Institution :
Bur. of Reclamation, Denver, CO, USA
Volume :
10
Issue :
3
fYear :
1995
fDate :
9/1/1995 12:00:00 AM
Firstpage :
538
Lastpage :
542
Abstract :
Modern excitation systems include devices for controlling or limiting machine terminal voltage (overvoltage limiters), volts per hertz ratio (V/Hz limiters), maximum machine field current (overexcitation limiters), and the reactive load absorbed by the machine (underexcitation limiters). Functional testing of these limiters before they are placed into commercial service is recommended. The Bureau of Reclamation (USA) routinely performs functional testing to determine the actual settings and operational characteristic of these limiters as part of excitation system commissioning tests on its hydroelectric generators. This paper discusses the purpose and practice of functionally testing these limiters
Keywords :
commissioning; exciters; hydroelectric generators; limiters; machine control; machine protection; machine testing; overvoltage protection; synchronous generators; turbogenerators; USA; actual settings; commissioning; excitation control systems; functional testing; hydroelectric generators; limiter performance; machine field current; machine terminal voltage; operational characteristics; overexcitation limiters; overvoltage limiters; reactive load; underexcitation limiters; volts per hertz ratio; Automatic voltage control; Control systems; Hydroelectric power generation; Modems; Performance evaluation; Protection; Protective relaying; Regulators; System testing; Voltage control;
fLanguage :
English
Journal_Title :
Energy Conversion, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8969
Type :
jour
DOI :
10.1109/60.464879
Filename :
464879
Link To Document :
بازگشت