    Verification of limiter performance in modern excitation control systems

  • Author

    Girgis, George K. ; Vu, Hoa D.

  • Author_Institution
    Bur. of Reclamation, Denver, CO, USA
  • Volume
    10
  • Issue
    3
  • fYear
    1995
  • fDate
    9/1/1995 12:00:00 AM
  • Firstpage
    538
  • Lastpage
    542
  • Abstract
    Modern excitation systems include devices for controlling or limiting machine terminal voltage (overvoltage limiters), volts per hertz ratio (V/Hz limiters), maximum machine field current (overexcitation limiters), and the reactive load absorbed by the machine (underexcitation limiters). Functional testing of these limiters before they are placed into commercial service is recommended. The Bureau of Reclamation (USA) routinely performs functional testing to determine the actual settings and operational characteristic of these limiters as part of excitation system commissioning tests on its hydroelectric generators. This paper discusses the purpose and practice of functionally testing these limiters
  • Keywords
    commissioning; exciters; hydroelectric generators; limiters; machine control; machine protection; machine testing; overvoltage protection; synchronous generators; turbogenerators; USA; actual settings; commissioning; excitation control systems; functional testing; hydroelectric generators; limiter performance; machine field current; machine terminal voltage; operational characteristics; overexcitation limiters; overvoltage limiters; reactive load; underexcitation limiters; volts per hertz ratio; Automatic voltage control; Control systems; Hydroelectric power generation; Modems; Performance evaluation; Protection; Protective relaying; Regulators; System testing; Voltage control;
  • fLanguage
    English
  • Journal_Title
    Energy Conversion, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8969
  • Type

    jour

  • DOI
    10.1109/60.464879
  • Filename
    464879