DocumentCode :
966868
Title :
Numerical Analysis of DC Current Distribution in AC Power System Near HVDC System
Author :
Zhang, Bo ; Zhao, Jie ; Zeng, Rong ; He, Jinliang
Author_Institution :
Tsinghua Univ., Beijing
Volume :
23
Issue :
2
fYear :
2008
fDate :
4/1/2008 12:00:00 AM
Firstpage :
960
Lastpage :
965
Abstract :
When dc current is injected into the earth through the grounding electrodes of an HVDC system, transformers in an ac system may be under dc bias if the dc currents flowing through the transformers are large enough. In this paper, a circuit model is presented to calculate the dc current distribution in an ac power system caused by the ground return current of a dc system. A complex image method is used to calculate the ground potential rise of each substation in multilayer earth. An indirect boundary element method is used to take into account the effects of mountains, rivers, and sea. The circuit equations are used to take into account the effects of the transmission lines. By using the method, the dc current distribution and the effectiveness of restraining measure in an ac power system are analyzed. The method and the results are not only useful for analyzing the influence of the ground return current from an HVDC ground electrode on ac power systems, but also useful for analyzing the effectiveness of the restraining measure.
Keywords :
HVDC power convertors; HVDC power transmission; current distribution; electrochemical electrodes; HVDC system; ac power system; complex image method; dc current distribution; ground return current; grounding electrodes; indirect boundary element method; multilayer earth; transformers; transmission lines; Current distribution; HVDC transmission; grounding electrodes; power systems; transformers;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/TPWRD.2007.908748
Filename :
4378287
Link To Document :