• DocumentCode
    975922
  • Title

    Application of unique measuring techniques to positive impulse corona stabilisation in SF6

  • Author

    Van Der Zel, G.L. ; Reynders, J.P.

  • Author_Institution
    ESKOM Technol., Cleveland, South Africa
  • Volume
    143
  • Issue
    3
  • fYear
    1996
  • fDate
    5/1/1996 12:00:00 AM
  • Firstpage
    182
  • Lastpage
    186
  • Abstract
    Results of the application of unique measuring tools for corona stabilisation under positive impulse conditions in SF6 are presented. The present postulate that corona stabilisation appears and disappears about a distinct threshold of impulse rise-time of approximately 10 μs is tested. For slow-rising impulses (>10 μs), breakdown is found to be able to occur both with and without corona stabilisation. The measurements are explained by the availability of free electrons during the rise-time of the impulse. The unique measuring tools applied rely on statistical analysis of records of the final spark path and correlation of this data with the time-to-breakdown data. The results of the measuring tools are initially verified through tests under conditions of known corona stabilisation
  • Keywords
    SF6 insulation; corona; electric breakdown; flashover; gas insulated substations; sparks; statistical analysis; 0 to 600 mus; SF6; data correlation; electric strength; final spark path; free electrons; gas insulated substation; gaseous insulation; impulse rise-time threshold; measuring tools; positive impulse corona stabilisation; spark launch angles; statistical analysis; time-to-breakdown;
  • fLanguage
    English
  • Journal_Title
    Science, Measurement and Technology, IEE Proceedings -
  • Publisher
    iet
  • ISSN
    1350-2344
  • Type

    jour

  • DOI
    10.1049/ip-smt:19960310
  • Filename