Application of unique measuring techniques to positive impulse corona stabilisation in SF6
Author
Van Der Zel, G.L. ; Reynders, J.P.
Author_Institution
ESKOM Technol., Cleveland, South Africa
Volume
143
Issue
3
fYear
1996
fDate
5/1/1996 12:00:00 AM
Firstpage
182
Lastpage
186
Abstract
Results of the application of unique measuring tools for corona stabilisation under positive impulse conditions in SF6 are presented. The present postulate that corona stabilisation appears and disappears about a distinct threshold of impulse rise-time of approximately 10 μs is tested. For slow-rising impulses (>10 μs), breakdown is found to be able to occur both with and without corona stabilisation. The measurements are explained by the availability of free electrons during the rise-time of the impulse. The unique measuring tools applied rely on statistical analysis of records of the final spark path and correlation of this data with the time-to-breakdown data. The results of the measuring tools are initially verified through tests under conditions of known corona stabilisation
Keywords
SF6 insulation; corona; electric breakdown; flashover; gas insulated substations; sparks; statistical analysis; 0 to 600 mus; SF6; data correlation; electric strength; final spark path; free electrons; gas insulated substation; gaseous insulation; impulse rise-time threshold; measuring tools; positive impulse corona stabilisation; spark launch angles; statistical analysis; time-to-breakdown;
fLanguage
English
Journal_Title
Science, Measurement and Technology, IEE Proceedings -
Publisher
iet
ISSN
1350-2344
Type
jour
DOI
10.1049/ip-smt:19960310
Filename
502437
Link To Document