Title : 
Application of unique measuring techniques to positive impulse corona stabilisation in SF6
         
        
            Author : 
Van Der Zel, G.L. ; Reynders, J.P.
         
        
            Author_Institution : 
ESKOM Technol., Cleveland, South Africa
         
        
        
        
        
            fDate : 
5/1/1996 12:00:00 AM
         
        
        
        
            Abstract : 
Results of the application of unique measuring tools for corona stabilisation under positive impulse conditions in SF6 are presented. The present postulate that corona stabilisation appears and disappears about a distinct threshold of impulse rise-time of approximately 10 μs is tested. For slow-rising impulses (>10 μs), breakdown is found to be able to occur both with and without corona stabilisation. The measurements are explained by the availability of free electrons during the rise-time of the impulse. The unique measuring tools applied rely on statistical analysis of records of the final spark path and correlation of this data with the time-to-breakdown data. The results of the measuring tools are initially verified through tests under conditions of known corona stabilisation
         
        
            Keywords : 
SF6 insulation; corona; electric breakdown; flashover; gas insulated substations; sparks; statistical analysis; 0 to 600 mus; SF6; data correlation; electric strength; final spark path; free electrons; gas insulated substation; gaseous insulation; impulse rise-time threshold; measuring tools; positive impulse corona stabilisation; spark launch angles; statistical analysis; time-to-breakdown;
         
        
        
            Journal_Title : 
Science, Measurement and Technology, IEE Proceedings -
         
        
        
        
        
            DOI : 
10.1049/ip-smt:19960310