• DocumentCode
    977336
  • Title

    Current transformer performance with steady-state DC biasing

  • Author

    Emanuel, A.

  • Author_Institution
    Worcester Polytechnic Institute, Worcester, MA
  • Volume
    16
  • Issue
    5
  • fYear
    1980
  • fDate
    9/1/1980 12:00:00 AM
  • Firstpage
    1278
  • Lastpage
    1282
  • Abstract
    The accuracy of current transformers with steady-state dc biasing is estimated by considering a single-valued equivalent magnetizing characteristic and the core losses. Theoretical results confirmed by experimental measurements show that, for metering class transformers built with high-permeability cores, dc biasing level in excess of 0.5 percent rated rms current may cause unacceptable errors.
  • Keywords
    Current transformers; Algebra; Current transformers; DC-DC power converters; Electrons; Inductors; Magnetic cores; Power supplies; Power transformers; Steady-state; Transformer cores;
  • fLanguage
    English
  • Journal_Title
    Magnetics, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9464
  • Type

    jour

  • DOI
    10.1109/TMAG.1980.1060840
  • Filename