Title : 
Current transformer performance with steady-state DC biasing
         
        
        
            Author_Institution : 
Worcester Polytechnic Institute, Worcester, MA
         
        
        
        
        
            fDate : 
9/1/1980 12:00:00 AM
         
        
        
        
            Abstract : 
The accuracy of current transformers with steady-state dc biasing is estimated by considering a single-valued equivalent magnetizing characteristic and the core losses. Theoretical results confirmed by experimental measurements show that, for metering class transformers built with high-permeability cores, dc biasing level in excess of 0.5 percent rated rms current may cause unacceptable errors.
         
        
            Keywords : 
Current transformers; Algebra; Current transformers; DC-DC power converters; Electrons; Inductors; Magnetic cores; Power supplies; Power transformers; Steady-state; Transformer cores;
         
        
        
            Journal_Title : 
Magnetics, IEEE Transactions on
         
        
        
        
        
            DOI : 