Title :
Digital simulation, transient network analyzer and field tests of the closed loop control of the Eddy County SVC
Author :
Bergmann, Karel ; Friedrich, Bernd G. ; Stump, Keith ; Elliott, William H.
Author_Institution :
Siemens AG, Erlangen, Germany
fDate :
10/1/1993 12:00:00 AM
Abstract :
A static VAr compensator (SVC) was installed at the Eddy County substation near Artesia, New Mexico. It was put into commercial operation in April 1992. Before the commissioning period, a phase of extensive testing and analysis of the digital closed loop control was undertaken. This work was done using the actual control hardware and software in conjunction with an analog TNA and with digital simulation models of control and power systems. Results of this work were checked with the power system during field commissioning of the SVC. This paper gives an overview of the closed loop control design. It presents some results from the TNA tests, digital simulation and commissioning field tests of the SVC operation
Keywords :
closed loop systems; digital simulation; power system analysis computing; power system computer control; power system transients; static VAr compensators; substations; transient analysers; Artesia; Eddy County SVC; New Mexico; digital closed loop control; digital simulation models; field tests; power system; static VAr compensator; transient network analyzer; Digital simulation; Power system analysis computing; Power system control; Power system modeling; Power system simulation; Power system transients; Static VAr compensators; Substations; Testing; Transient analysis;
Journal_Title :
Power Delivery, IEEE Transactions on