DocumentCode :
981873
Title :
Harmonic interaction between generation and transmission systems
Author :
Medina, A. ; Arrillaga, J.
Author_Institution :
Canterbury Univ., Christchurch, New Zealand
Volume :
8
Issue :
4
fYear :
1993
fDate :
10/1/1993 12:00:00 AM
Firstpage :
1981
Lastpage :
1987
Abstract :
Simulation of the harmonic interaction between detailed models of the synchronous generator, power transformer and transmission system is achieved with the development of a unified multifrequency domain equivalent. The model incorporates detailed models of the generator harmonic conversion and magnetic saturation, multilimb core saturation electrical winding connections, mutual coupling between windings and harmonic contribution of the transmission system. The results are compared with the network harmonic response using a conventional generator representation
Keywords :
frequency-domain analysis; harmonics; power transformers; synchronous generators; transmission networks; windings; electrical winding connections; generator harmonic conversion; harmonic interaction; magnetic saturation; multilimb core saturation; mutual coupling; network harmonic response; power transformer; synchronous generator; transmission system; unified multifrequency domain equivalent; Circuit faults; Magnetic flux; Mutual coupling; Power generation; Power system harmonics; Power system modeling; Power transformers; Saturation magnetization; Synchronous generators; Transformer cores;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.248311
Filename :
248311
Link To Document :
بازگشت