Abstract :
A previously developed method of partial discharge (PD) recognition is used to evaluate PD in HV devices. Using conventional discharge detection (bandwidth ~400 kHz), the PD patterns are studied. By means of unambiguous statistical operators like skewness, kurtosis, number of peaks, etc., quantitative information about the discharge source can be obtained. In the case of an unknown defect, a combination of these operators is compared to the same set of operators for a known configuration. In this way, a statement can be made on the character of a discharge source. The use of this technique in evaluating different discharges in HV cable and in 400 kV SF6 insulation confirms the usefulness of the new approach
Keywords :
automatic test equipment; cable testing; electric variables measurement; high-voltage techniques; insulation testing; partial discharges; pattern recognition; statistical analysis; 400 kHz; 400 kV; HV cable; HV equipment; PD measurement; PD patterns; PD recognition; SF6; SF6 insulation; computer-aided measurement; discharge source; partial discharges; statistical operators; Automatic testing; Bandwidth; Cable insulation; Dielectrics and electrical insulation; Fault location; Laboratories; Partial discharges; Pattern recognition; Shape; System testing;
fLanguage :
English
Journal_Title :
Electrical Insulation, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9367
Type :
jour
DOI :
10.1109/14.249370
Filename :
249370
Link To Document :
بازگشت