Title :
Influence of transformer core design on power losses
Author :
Valkovic, Zvonimir
Author_Institution :
Institue Rade Koncar, Zagreb, Yugoslavia
fDate :
3/1/1982 12:00:00 AM
Abstract :
The results of an experimental investigation on reduced models of the influence of core design on core losses are presented. The characteristics of single-phase and three-phase three-limbed cores are compared, and the influence of the core proportions on the core building factor is determined. Four types of T-joint design for a three-phase core have been investigated. It has been found that the widely applied V-45° T-joint does not have the best magnetic properties, as usually assumed. The influence of the corner joint overlap length, the number of laminations per stagger layer, and the yoke cross-section form on the core building factor have been determined.
Keywords :
Magnetic core losses; Power transformers; Buildings; Coils; Core loss; Helium; Lamination; Magnetic cores; Magnetic materials; Magnetic properties; Steel; Transformer cores;
Journal_Title :
Magnetics, IEEE Transactions on
DOI :
10.1109/TMAG.1982.1061824