• DocumentCode
    988921
  • Title

    A novel algorithm to determine minimum break point set for optimum cooperation of directional protection relays in multiloop networks

  • Author

    Yue, Quanming ; Lu, Feipeng ; Yu, Weiyong ; Wang, Jie

  • Author_Institution
    Dept. of Electr. Eng., Shanghai Jiaotong Univ., China
  • Volume
    21
  • Issue
    3
  • fYear
    2006
  • fDate
    7/1/2006 12:00:00 AM
  • Firstpage
    1114
  • Lastpage
    1119
  • Abstract
    Determining minimum break point set (MBPS) is necessary before setting distance protection relays or zero-sequence protection relays in multiloop extremely high voltage power networks. Determining directional simple loops (DSLs) and relative sequence groups (RSGs) is the prerequisite of traditional algorithms which are used to determine MBPS. In order to reduce the CPU time and complexity of calculating MBPS, a new concept named as protection relay dependency dimension (PRDD) is presented for the first time in this paper. By comparison of PRDD in a multiloop network, the MBPS can be determined, and the process of comparisons will not stop until the MBPS of the multiloop networks is discovered. In the meantime, the RSG could be easily determined by means of judging whether the primary protection relay set of a protection relay is null or not. The new algorithm leaves out those laborious steps, such as determining all of the DSLs and RSGs. Some examples are given to illuminate the novel algorithm presented in the paper to be simple and effective.
  • Keywords
    power system protection; relay protection; directional protection relays; directional simple loop; high voltage power networks; minimum break point set determination; multiloop networks; protection relay dependency dimension; relative sequence groups; zero-sequence protection relays; Artificial neural networks; Central Processing Unit; Cities and towns; Computer networks; DSL; Graph theory; Intelligent networks; Protection; Protective relaying; Voltage; Directional protection relay; minimum break point set (MBPS); primary protection relay set (PPRS); protection relay dependency dimension (PRDD); relative sequence group (RSG); setting and calculation;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/TPWRD.2005.861333
  • Filename
    1645145