Title :
A series multiresolution morphological gradient-based criterion to identify CT saturation
Author :
Lin, Xiangning ; Zou, Li ; Tian, Qing ; Weng, Hanli ; Liu, Pei
Author_Institution :
Huazhong Univ. of Sci. & Technol., Hubei, China
fDate :
7/1/2006 12:00:00 AM
Abstract :
The differential relay possibly mal-operate due to the inconsistent transforming characteristics of current transformers (CTs) when experiencing heavy through fault. According to the investigation of CTs of differential protection, the time interval between the occurrence of differential current and the sudden change of phase current can be utilized to distinguish between the external faults and the internal faults. A new CT saturation-blocking scheme for differential protections, which aims at identifying this time interval by virtue of series multiresolution morphological gradient (SMMG) is proposed. Using the excellent singularity detecting together with the noise-repressing abilities of SMMG, this time interval can be identified in real time with high accuracy. The EMTDC-based simulation results show that the scheme can effectively prevent the differential protection from mal-operating meanwhile guarantee the high-speed response to the internal fault.
Keywords :
current transformers; fault diagnosis; gradient methods; mathematical morphology; power transformer protection; CT saturation identification; ETMDC; current transformers; differential current; differential protection; external faults; internal faults; phase current; saturation blocking scheme; series multiresolution morphological gradient; Circuit faults; Current transformers; Energy resolution; Fault currents; Fault diagnosis; Helium; Morphology; Protection; Protective relaying; Transmission lines; Current-transformer (CT) saturation; differential protection; mathematical morphology; series multiresolution morphological gradient;
Journal_Title :
Power Delivery, IEEE Transactions on
DOI :
10.1109/TPWRD.2005.861338