DocumentCode
989213
Title
Analysis of some measurement issues in bushing power factor tests in the field
Author
Zhang, S.
Author_Institution
PCORE Electr. Co. Inc., LeRoy, NY, USA
Volume
21
Issue
3
fYear
2006
fDate
7/1/2006 12:00:00 AM
Firstpage
1350
Lastpage
1356
Abstract
The power factor measurement is widely used in the evaluation of bushing insulation conditions in the field. Some measurement issues occur in the field tests which give abnormal readings of bushing C1 and/or C2 power factors. This paper provides an engineering analysis of the possible measurement issues in the bushing field tests such as testing a bushing on a transformer or in its shipping crate, or a bushing with wet/contaminated voltage/test tap or wet/dirty porcelain surface.
Keywords
bushings; power factor measurement; testing; bushing insulation conditions; bushing power factor tests; porcelain; power factor measurement; shipping crate; transformer; Circuit testing; Insulation testing; Insulators; Oil insulation; Pollution measurement; Power measurement; Power transformer insulation; Reactive power; Transformer cores; Windings; Bushing; crate; porcelain; power factor; test tap; transformer; voltage tap;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/TPWRD.2006.874616
Filename