DocumentCode :
989744
Title :
Analytical calculation and stochastic assessment of voltage sags
Author :
Moschakis, M.N. ; Hatziargyriou, N.D.
Author_Institution :
Sch. of Electr. & Comput. Eng., Nat. Tech. Univ. of Athens, Greece
Volume :
21
Issue :
3
fYear :
2006
fDate :
7/1/2006 12:00:00 AM
Firstpage :
1727
Lastpage :
1734
Abstract :
In this paper, analytical expressions for the calculation of voltage sag magnitude due to faults at every point of a meshed or radial power network are derived. Balanced and unbalanced faults are considered and the effect of power transformers is taken into account. The following methods for stochastic assessment of voltage sag magnitude are compared using these expressions: the method of critical distances, method of fault positions, and Monte Carlo method. The minimum required number of fault positions and iterations assumed by the two methods in order to achieve results of acceptable accuracy are determined.
Keywords :
Monte Carlo methods; fault diagnosis; power supply quality; power transformers; stochastic processes; Monte Carlo methods; fault positions; power transformers; radial power networks; stochastic assessment; unbalanced faults; voltage sags; Circuit faults; Electrical equipment industry; Impedance; Monte Carlo methods; Power quality; Power system faults; Power transformers; Stochastic processes; System testing; Voltage fluctuations; Critical distance; Monte Carlo; fault positions; power system analysis; voltage sags;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/TPWRD.2006.874108