• DocumentCode
    990180
  • Title

    Reduction of Sheath Losses in Single-Conductor Cables

  • Author

    Halperin, Herman ; Miller, K.W.

  • Author_Institution
    Head Engineer and Asst. Head Engineer, Technical Division, Street Department, Commonwealth Edison Company, Chicago, Ill.
  • Volume
    48
  • Issue
    2
  • fYear
    1929
  • fDate
    4/1/1929 12:00:00 AM
  • Firstpage
    399
  • Lastpage
    414
  • Abstract
    The use of single-conductor, lead-covered cable for high-voltage, three-phase transmission lines results in sheath losses ranging from 25 to 300 per cent of the conductor losses for cables installed in separate ducts, unless special methods for the reduction of the losses are used. Some of these methods, while practically eliminating sheath losses, cause a-c. sheath potentials which may be injurious. In this connection the authors have developed a new scheme of bonding and a new bonding device, which appear to have marked advantages. This article consists of a general discussion relative to the reduction of sheath losses with special reference to laboratory tests and field work done on 132 miles of single-conductor cable of the Commonwealth Edison Company. The economics of sheath losses and of the methods for their practical elimination are discussed. The theories of sheath losses and induced voltages are outlined and correlated, and new formulas and curves are developed. An analytical and graphical comparison of sheath bonding connections is presented. Investigations are reported on tests regarding the nature and extent of possible corrosion of sheaths caused by a-c. sheath voltages.
  • Keywords
    Bonding; Cables; Conductors; Corrosion; Costs; Ducts; Investments; Propagation losses; Testing; Voltage;
  • fLanguage
    English
  • Journal_Title
    American Institute of Electrical Engineers, Transactions of the
  • Publisher
    ieee
  • ISSN
    0096-3860
  • Type

    jour

  • DOI
    10.1109/T-AIEE.1929.5055229
  • Filename