• DocumentCode
    992032
  • Title

    Arc-fault protection of branch circuits, cords, and connected equipment

  • Author

    Parise, Giuseppe ; Martirano, Luigi ; Nabours, Robert E.

  • Author_Institution
    Electr. Eng. Dept., Univ. of Rome "La Sapienza", Italy
  • Volume
    40
  • Issue
    3
  • fYear
    2004
  • Firstpage
    896
  • Lastpage
    899
  • Abstract
    In electrical power systems, the fault frequently involves arcing and burning of wiring exposed to mechanical damage and other insulation stresses including wiring not fixed and connected by flexible cords and cables. IEC Standard 60364 ends the design of electric power systems at the outlets of branch circuits or at the fixed equipment. A complete design should include the connections of portable equipment and of extension cords (as requested by NFPA 70) that are exposed to arc faults and may cause fire and/or electric shock hazards. Since cords supplying Class II equipment are without a grounding protection conductor, the failure of the double insulation, caused by external damage, is unlikely to be easily detected as a ground fault. Protection must be provided to prevent the fault from extinguishing itself without being detected and remaining energized, thus presenting an electric shock hazard by direct contact with a live part, rendered accessible after local insulation failure. The authors highlight this worst case and suggest the protection achieved by wiring the circuits, particularly extension cords, with special power cables. Ground-fault forced cables (GFFCs) convert a line-to-line fault into a line-to-ground fault, that will be detected and protected by ordinary ground-fault protective devices. By adopting the GFFC type of cables internally to Class II equipment, the disconnecting protection could also be extended to equipment.
  • Keywords
    arcs (electric); earthing; power cables; power system faults; power system protection; arc-fault protection; arcing; branch circuits; circuit protection; electrical power systems; extension cords; flexible cords; ground-fault forced cables; wire burning; Cable insulation; Circuit faults; Dielectrics and electrical insulation; Electric shock; Electrical fault detection; Hazards; Power system faults; Power system protection; Stress; Wiring; Arcing fault; circuit protection;
  • fLanguage
    English
  • Journal_Title
    Industry Applications, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0093-9994
  • Type

    jour

  • DOI
    10.1109/TIA.2004.827474
  • Filename
    1300745