DocumentCode
994143
Title
Effect of Transient Voltage on Power Transformer Design The Behavior of Transformers with Neutral Isolated or Grounded through an Impedance
Author
Palueff, K.K.
Author_Institution
General Electric Company, Pittsfield, Mass.
Volume
49
Issue
3
fYear
1930
fDate
7/1/1930 12:00:00 AM
Firstpage
1179
Lastpage
1190
Abstract
The results of theoretical and oscillographic study of transient voltage phenomena in shell type and core type transformers with neutral isolated from ground, and also with neutral grounded through impedances of different characteristics are briefly described. In the case of isolated neutral, the majority of lightning traveling waves cause the potential of the entire winding, including neutral, to rise above ground to a value at least equal to the applied voltage. In the case of switching surges, the voltage of the neutral, as well as of the rest of the winding, is apt to rise to a value considerably in excess of the applied voltage. In the case of transformers excited with damped oscillations similar to switching surges, oscillographic records of both shell and core type transformers indicate internal voltages to ground approximately four times the applied. Grounding of a transformer through resistance, inductance, or capacitance does not reduce the above internal transient voltages, unless a certain relation is established between these constants, the constants of the transformer circuit, and the wave shape of the line surge. If the proper relation of these constants is established, then internal transient voltages are reduced practically to those of a solidly grounded transformer. A grounding device, called an ``impedor,´´ can be designed to have impedance at operating frequency equal to any desired value and to act at transient voltage frequencies as if its impedance were practically zero.
Keywords
Capacitance; Frequency; Grounding; Impedance; Inductance; Lightning; Oscillators; Power transformers; Surges; Transformer cores;
fLanguage
English
Journal_Title
American Institute of Electrical Engineers, Transactions of the
Publisher
ieee
ISSN
0096-3860
Type
jour
DOI
10.1109/T-AIEE.1930.5055639
Filename
5055639
Link To Document