• DocumentCode
    997314
  • Title

    Performance study of two different compensating devices in a custom power park

  • Author

    Ghosh, A.

  • Author_Institution
    Dept. of Electr. Eng., Indian Inst. of Technol., Kanpur, India
  • Volume
    152
  • Issue
    4
  • fYear
    2005
  • fDate
    7/8/2005 12:00:00 AM
  • Firstpage
    521
  • Lastpage
    528
  • Abstract
    Simulation study of a custom power park (CPP) is presented. It is assumed that the park contains unbalanced and nonlinear loads in addition to a sensitive load. Two different types of compensators are used separately to protect the sensitive load against unbalance and distortion caused by the other loads. It has been shown that a shunt compensator can regulate the voltage of the CPP bus, whereas the series compensator can only regulate the sensitive load terminal voltage. Additional issues such as the load transfer through a static transfer switch, detection of sag/fault etc. are also discussed. The concepts are validated through PSCAD/EMTDC simulation studies on a sample distribution system.
  • Keywords
    fault location; power distribution control; power distribution faults; power distribution protection; power system CAD; power system simulation; switches; voltage control; PSCAD-EMTDC simulation; compensation device; custom power park; distribution system; fault detection; load transfer; nonlinear load; sensitive load; static transfer switch; voltage regulation;
  • fLanguage
    English
  • Journal_Title
    Generation, Transmission and Distribution, IEE Proceedings-
  • Publisher
    iet
  • ISSN
    1350-2360
  • Type

    jour

  • DOI
    10.1049/ip-gtd:20045014
  • Filename