DocumentCode :
997314
Title :
Performance study of two different compensating devices in a custom power park
Author :
Ghosh, A.
Author_Institution :
Dept. of Electr. Eng., Indian Inst. of Technol., Kanpur, India
Volume :
152
Issue :
4
fYear :
2005
fDate :
7/8/2005 12:00:00 AM
Firstpage :
521
Lastpage :
528
Abstract :
Simulation study of a custom power park (CPP) is presented. It is assumed that the park contains unbalanced and nonlinear loads in addition to a sensitive load. Two different types of compensators are used separately to protect the sensitive load against unbalance and distortion caused by the other loads. It has been shown that a shunt compensator can regulate the voltage of the CPP bus, whereas the series compensator can only regulate the sensitive load terminal voltage. Additional issues such as the load transfer through a static transfer switch, detection of sag/fault etc. are also discussed. The concepts are validated through PSCAD/EMTDC simulation studies on a sample distribution system.
Keywords :
fault location; power distribution control; power distribution faults; power distribution protection; power system CAD; power system simulation; switches; voltage control; PSCAD-EMTDC simulation; compensation device; custom power park; distribution system; fault detection; load transfer; nonlinear load; sensitive load; static transfer switch; voltage regulation;
fLanguage :
English
Journal_Title :
Generation, Transmission and Distribution, IEE Proceedings-
Publisher :
iet
ISSN :
1350-2360
Type :
jour
DOI :
10.1049/ip-gtd:20045014
Filename :
1467954
Link To Document :
بازگشت