DocumentCode
997429
Title
Impact of Arc Flash Hazards on Medium-Voltage Switchgear
Author
Shah, Kanu R. ; Cinsavich, Alan L. ; De Silva, Priyan
Author_Institution
Shah & Assoc., Inc., Gaithersburg, MD
Volume
44
Issue
6
fYear
2008
Firstpage
1859
Lastpage
1863
Abstract
This paper discusses the arc flash ramifications associated with the design and selection of medium-voltage switchgear. Three case studies are presented to demonstrate the impact of performing arc flash hazard analysis on the proposed and/or existing medium-voltage installation at the design stage. This paper proposes the following: 1) changes in the National Electrical Code, Article 110.16, to provide mandatory requirements for a) performing arc flash analysis at the design stage and b) placement of warning labels on switchgear to warn qualified persons of potential arc flash hazards and 2) a need to promulgate regulations requiring a utility company to notify its customers of changes in a) the available fault duty at the point of common coupling with a customer´s facility and b) utility upstream protective device settings.
Keywords
arcs (electric); flashover; switchgear; National Electrical Code; arc flash hazards; medium-voltage installation; medium-voltage switchgear; point of common coupling; promulgate regulations; protective device; warning labels; Hazards; Industrial control; Industry Applications Society; Medium voltage; National electric code; Performance analysis; Procurement; Sockets; Substation protection; Switchgear; Arc flash hazard analysis; flash protection; hazard/risk category (HRC); incident energy level; personal protective equipment (PPE); protective devices;
fLanguage
English
Journal_Title
Industry Applications, IEEE Transactions on
Publisher
ieee
ISSN
0093-9994
Type
jour
DOI
10.1109/TIA.2008.2006299
Filename
4681950