DocumentCode
997931
Title
Hydro-Quebec´s concerns related to performances of SF/sub 6/ circuit-breakers
Author
Beauchemin, Roger ; Latour, Yves ; Landry, Michel ; Riffon, Pierre
Author_Institution
Hydro-Quebec, Montreal, Que., Canada
Volume
8
Issue
3
fYear
1993
fDate
7/1/1993 12:00:00 AM
Firstpage
1123
Lastpage
1129
Abstract
Hydro-Quebec´s concerns regarding circuit breaker reliability are presented. Emphasis is placed on two aspects crucial in determining line charging current breaking capacity, i.e., the arc duration and the test circuit configuration. The importance of manufacturing quality for the arcing contacts, nozzles and gasket is discussed. Test criteria at 20 degrees C for simulating breaking tests at -50 degrees C are given. Hydro-Quebec´s requirements for testing the tightness of SF/sub 6/ breakers are presented together with a reliable leakage-measuring method.<>
Keywords
circuit breakers; circuit-breaking arcs; gaseous insulation; leak detection; quality control; reliability; sulphur compounds; switchgear testing; -50 degC; 20 degC; Canada; GIS; Hydro-Quebec; SF/sub 6/; arc duration; arcing contacts; circuit breaker; gasket; leak detection; line charging current breaking capacity; manufacturing quality; nozzles; performances; reliability; switchgear testing; test circuit; tightness;