• DocumentCode
    997931
  • Title

    Hydro-Quebec´s concerns related to performances of SF/sub 6/ circuit-breakers

  • Author

    Beauchemin, Roger ; Latour, Yves ; Landry, Michel ; Riffon, Pierre

  • Author_Institution
    Hydro-Quebec, Montreal, Que., Canada
  • Volume
    8
  • Issue
    3
  • fYear
    1993
  • fDate
    7/1/1993 12:00:00 AM
  • Firstpage
    1123
  • Lastpage
    1129
  • Abstract
    Hydro-Quebec´s concerns regarding circuit breaker reliability are presented. Emphasis is placed on two aspects crucial in determining line charging current breaking capacity, i.e., the arc duration and the test circuit configuration. The importance of manufacturing quality for the arcing contacts, nozzles and gasket is discussed. Test criteria at 20 degrees C for simulating breaking tests at -50 degrees C are given. Hydro-Quebec´s requirements for testing the tightness of SF/sub 6/ breakers are presented together with a reliable leakage-measuring method.<>
  • Keywords
    circuit breakers; circuit-breaking arcs; gaseous insulation; leak detection; quality control; reliability; sulphur compounds; switchgear testing; -50 degC; 20 degC; Canada; GIS; Hydro-Quebec; SF/sub 6/; arc duration; arcing contacts; circuit breaker; gasket; leak detection; line charging current breaking capacity; manufacturing quality; nozzles; performances; reliability; switchgear testing; test circuit; tightness;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.252599
  • Filename
    252599