• DocumentCode
    998085
  • Title

    An improved current-comparator-based 1000-A transconductance amplifier for the in-situ calibration of transformer loss measuring systems

  • Author

    Miljanic, Petar N. ; So, Eddy

  • Author_Institution
    Nat. Res. Council of Canada, Ottawa, Ont., Canada
  • Volume
    8
  • Issue
    3
  • fYear
    1993
  • fDate
    7/1/1993 12:00:00 AM
  • Firstpage
    861
  • Lastpage
    865
  • Abstract
    A current comparator technique and an error feedforward control strategy are applied to the design of a high current transconductance amplifier to obtain a highly stable and accurate output current. The transconductance amplifier features a current output range of 1000 A with a compliance voltage of 3 V. It has the ability to provide a highly accurate current to a circuit that is operated at high voltage. This high-current transconductance amplifier is used in a system for the in-situ calibration of transformer loss measuring systems. The output current has accuracies of better than +or-10 ppm (parts-per-million) in both magnitude and phase.<>
  • Keywords
    amplifiers; calibration; comparators (circuits); loss measurement; power transformers; 1000 A; 3 V; accuracy; compliance voltage; current comparator; design; error feedforward control; in-situ calibration; magnitude; phase; power transformers; transconductance amplifier; transformer loss measuring systems; transformer testing;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.252614
  • Filename
    252614