• DocumentCode
    998113
  • Title

    Verification of ANSI C37.90.1 SWC test generator outputs

  • Author

    Cooper, David M. ; Pettigrew, Robert D.

  • Author_Institution
    Cooper Circuits, Duluth, GA, USA
  • Volume
    8
  • Issue
    3
  • fYear
    1993
  • fDate
    7/1/1993 12:00:00 AM
  • Firstpage
    905
  • Lastpage
    914
  • Abstract
    Awareness of fast transient events in the electrical power environment has increased with the release of related test standards (ANSI C37.90.1 and IEC 801-4) and with increased usage of solid state circuits in utility equipment. Reliable measurement of the fast transient test waveforms and repeatable performance of test setups are persistent problems for equipment manufacturers and users. The construction, characterization, and usage of two high voltage test dividers for measurement of fast transient test waveforms are described. Measurements on a C37.90.1 (SWC) test generator are presented along with tutorial background. Proposals for changes to the ANSI C37.90.1 specification are included.<>
  • Keywords
    power system protection; relay protection; standards; surges; test equipment; testing; ANSI C37.90.1; HV; IEC 801-4; fast transient test waveforms; high voltage test dividers; performance; power system protection; relay testing; solid state circuits; test equipment; test standards;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.252617
  • Filename
    252617