DocumentCode :
998123
Title :
Negative-sequence overcurrent element application and coordination in distribution protection
Author :
Elneweihi, A.F. ; Schweitzer, E.O., III ; Feltis, M.W.
Author_Institution :
British Columbia Hydro, Vancouver, BC, Canada
Volume :
8
Issue :
3
fYear :
1993
fDate :
7/1/1993 12:00:00 AM
Firstpage :
915
Lastpage :
924
Abstract :
Negative-sequence overcurrent elements do not respond to balanced load and can thus be set to operate faster and more sensitively than phase overcurrent elements for phase-to-phase faults. It is demonstrated that on a radial distribution system negative-sequence overcurrent elements need only be coordinated with downstream phase overcurrent devices for phase-to-phase faults. Coordination for other fault types is then achieved with no further analysis required. The effects of negative-sequence load current and open phase conductors on negative-sequence overcurrent elements are discussed.<>
Keywords :
distribution networks; electrical faults; power system protection; application; coordination; distribution networks; negative-sequence load current; negative-sequence overcurrent elements; open phase conductors; phase-to-phase faults; power system protection;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.252618
Filename :
252618
Link To Document :