System separation equipment to minimize power system instability using generator´s angular-velocity measurements
Author :
Morioka, Y. ; Tomiyama, K. ; Arima, H. ; Sawai, R. ; Omata, K. ; Matsushima, T. ; Takagi, K. ; Ishibashi, A. ; Saito, H.
Author_Institution :
Kansai Electric Power Co. Inc., Osaka, Japan
Volume :
8
Issue :
3
fYear :
1993
fDate :
7/1/1993 12:00:00 AM
Firstpage :
941
Lastpage :
947
Abstract :
The purpose of the equipment described is to separate the power system when an out-of-step between two groups of generators within it is predicted. The out-of-step prediction method is based on the generator´s angular-velocity data measured by electromagnetic sensors and gears that are fastened directly to the rotors. The equipment was tested by the large-scale power system simulator APSA (Advanced Power System Analyzer) and was also field tested. The results are presented.<>
Keywords :
angular velocity measurement; digital simulation; electric generators; electric sensing devices; power system analysis computing; power system measurement; power system protection; rotors; APSA; angular-velocity measurements; digital simulation; electromagnetic sensors; gears; generators; multimachine; out-of-step; power system instability; power system protection; prediction method; rotors;