Abstract
An HVDC fault location scheme is described. It relies on very precise detection of the time of arrival of fault-created surges at both ends of the line. Such detection is achieved by a very accurate data acquisition and processing system combined with the time reference signals provided by a Global Positioning System receiver. Extensive digital simulation is carried out to determine the voltage and current waveforms, to identify the main sources of error, and to suggest possible compensation techniques.<>
Keywords
DC transmission networks; computerised instrumentation; data acquisition; digital simulation; fault location; power system analysis computing; power system measurement; radionavigation; satellite relay systems; surges; time measurement; DC transmission networks; GPS; Global Positioning System receiver; HVDC; application; compensation; computerised instrumentation; current waveforms; data acquisition; data processing; digital simulation; error; fault location; power system measurement; satellite time references; surges; voltage waveforms;