DocumentCode :
998662
Title :
Influence of load current on bipolar DC corona
Author :
Pedrow, Patrick D. ; Qin, Bai Lin ; Wang, Qing Yuan
Author_Institution :
Sch. of Electr. Eng. & Comput. Sci., Washington State Univ., Pullman, WA, USA
Volume :
8
Issue :
3
fYear :
1993
fDate :
7/1/1993 12:00:00 AM
Firstpage :
1443
Lastpage :
1450
Abstract :
Bipolar DC corona is known to be a strong function of conductor voltage but little is known about the influence of load current on bipolar corona. To evaluate the influence of load current, a bipolar cylindrical corona cage was constructed and operated with simulated DC load current flowing in the conductors. Measurements of load current, corona current, ion current density, and conductor temperature show that corona conductance is a function of load current. The load current depends on temperature rather than magnetic field.<>
Keywords :
DC power transmission; corona; load (electric); power system measurement; power transmission lines; HVDC transmission lines; bipolar DC corona; conductance; conductor temperature; conductor voltage; corona current; cylindrical corona cage; ion current density; load current; magnetic field; power system measurement;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.252671
Filename :
252671
Link To Document :