• DocumentCode
    998813
  • Title

    Active DC filter for HVDC system-a test installation in the Konti-Skan DC link at Lindome converter station

  • Author

    Zhang, Wenyan ; Asplund, Gunnar ; Aberg, Anders ; Jonsson, Ulf ; Loof, O.

  • Author_Institution
    ASEA Brown Boveri, Ludvika, Sweden
  • Volume
    8
  • Issue
    3
  • fYear
    1993
  • fDate
    7/1/1993 12:00:00 AM
  • Firstpage
    1599
  • Lastpage
    1606
  • Abstract
    An active DC filter installed in the Konti-Skan high-voltage DC (HVDC) link is described. The active DC filter is connected at the bottom of an existing passive DC filter. The active DC filter includes an optic harmonic current measuring unit, a control system, a protection and supervision system, a pulse width modulation (PWM) power amplifier, a high-frequency transformer, surge arrester, and coupling apparatus. The active DC filter is small and occupies little ground area. The performance of the active DC filter for eliminating the disturbing harmonics is excellent.<>
  • Keywords
    DC power transmission; active filters; electric current measurement; fibre optic sensors; power amplifiers; power convertors; power system harmonics; power system measurement; power system protection; pulse width modulation; surge protection; testing; DC link; HF transformers; HVDC; PWM; Sweden; active DC filter; control system; disturbing harmonics; installation; optic harmonic current measuring unit; performance; power amplifier; power convertors; power transformers; protection; pulse width modulation; supervision; surge arrester;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.252686
  • Filename
    252686