DocumentCode :
998865
Title :
Ferroresonant overvoltages in grounded wye-wye padmount transformers with low-loss silicon steel cores
Author :
Walling, R.A. ; Barker, K.D. ; Compton, T.M. ; Zimmerman, L.E.
Author_Institution :
GE Ind. & Power Syst., Schenectady, NY, USA
Volume :
8
Issue :
3
fYear :
1993
fDate :
7/1/1993 12:00:00 AM
Firstpage :
1647
Lastpage :
1660
Abstract :
Reduced no-load losses have resulted in increased susceptibility to ferroresonance of grounded wye-wye three-phase distribution transformers using five-leg silicon steel wound cores. The authors describe the results of an extensive test program which determined that overvoltages are directly related to the ratio of capacitive susceptance divided by core losses and that the conventional use of rated exciting current can be a misleading indicator of ferroresonance susceptibility.<>
Keywords :
circuit resonance; distribution networks; ferromagnetism; losses; overvoltage; power transformers; transformer cores; transformer testing; capacitive susceptance; cores; ferroresonance; grounded wye-wye padmount transformers; no-load losses; overvoltages; power transformers; rated exciting current; silicon steel; susceptibility; three-phase distribution transformers;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.252691
Filename :
252691
Link To Document :
بازگشت