Title of article :
An experimental study on variable air volume operation of ducted air-conditioning with digital scroll compressor and conventional scroll compressor
Author/Authors :
Hu Huang، نويسنده , , Qihe Li، نويسنده , , Dongxue Yuan، نويسنده , , Zhenchun Qin، نويسنده , , Zhongbin Zhang، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2008
Pages :
6
From page :
761
To page :
766
Abstract :
An experimental study on operation characteristics with variable air volume under refrigerating and heating condition of ducted air-conditioning (AC) unit with digital scroll compressor and conventional scroll compressor is conducted in this paper. The effects of air volume on the refrigerating (heating) capacity, input power, EER (COP), outlet temperature, discharge pressure, discharge temperature and suction pressure are studied. Compared with the ducted air-conditioning unit with conventional scroll compressor, the experimental results are the outlet temperature of ducted AC unit with digital scroll compressor is stable; the suction pressure and discharge pressure are normal; the discharge temperature drops a bit; the input power is lower. This shows that the unit with digital scroll compressor is well adapted to the variable air volume running and good for the economical and reliable operation of the ducted AC unit.
Keywords :
Refrigerating , Heating , Variable air volume , Ducted unit , Digital scroll compressor
Journal title :
Applied Thermal Engineering
Serial Year :
2008
Journal title :
Applied Thermal Engineering
Record number :
1041571