Title of article :
Smoke triggered corona discharge sensor
Author/Authors :
Z. Mokhtari، نويسنده , , S. Holé، نويسنده , , J. Lewiner، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2013
Pages :
4
From page :
769
To page :
772
Abstract :
This paper presents an ionic smoke sensor working without a radioactive ionization source. The presence of smoke particles reduces significantly the effective corona discharge threshold of air by a factor greater than 5. The smoke sensor consists of a wire under an intermediate continuous voltage which generates a current only in presence of smoke. The sensor electric consumption is therefore very low and can operate for a long time. Results of a prototype operating under 600 V with a 25-μm-diameter wire are shown.
Keywords :
Smokesensor , Coronadischarge , Thresholdmodification
Journal title :
JOURNAL OF ELECTROSTATICS
Serial Year :
2013
Journal title :
JOURNAL OF ELECTROSTATICS
Record number :
1265538
Link To Document :
بازگشت