Title of article :
CFD model of the airflow, heat and mass transfer in cool stores
Author/Authors :
Nahor، نويسنده , , H.B. and Hoang، نويسنده , , M.L. and Verboven، نويسنده , , P. and Baelmans، نويسنده , , M. and Nicolaï، نويسنده , , B.M.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2005
Pages :
13
From page :
368
To page :
380
Abstract :
A transient three-dimensional CFD model was developed to calculate the velocity, temperature and moisture distribution in an existing empty and loaded cool store. The dynamic behaviour of the fan and cooler was modelled. The model accounted for turbulence by means of the standard k-ε model with standard wall profiles. The model was validated by means of velocity, air and product temperature. An average accuracy of 22% on the velocity magnitudes inside the empty cold store was achieved and the predicted temperature distribution was more uniform than predicted. In the loaded cold store, an average accuracy of 20% on the velocity magnitudes was observed. The model was capable of predicting both the air and product temperature with reasonable accuracy.
Keywords :
Modelling , Humidite´ , heat transfer , Mass transfer , Speed , Temperature , Mode´lisation , Transfert de chaleur , Transfert de masse , Dynamique des fluides , Vitesse , Cold store , Tempe´rature , Entrepoˆt frigorifique , Air , CFD , Humidity , Air
Journal title :
International Journal of Refrigeration
Serial Year :
2005
Journal title :
International Journal of Refrigeration
Record number :
1339830
Link To Document :
بازگشت