Title of article :
SF6 dielectric behaviour in a high voltage circuit breaker at low temperature under lightning impulses
Author/Authors :
Buret، نويسنده , , F.، نويسنده , , Beroual، نويسنده , , A.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 1996
Abstract :
This work concerns the study of the dielectric and
thermodynamic behaviour of SF, in a 145 kV circuit breaker
subjected to lightning impulse voltages in both polarities at temperatures
varying from ambient (20%) to - 45°C. The filling of
the circuit breaker with SFg is carried out at the reference point:
T = 15"C, P = 6 bars abs. and d = 39.6 kg/m3.
Devices allowing to detect the appearance of local condensation
of SF6 and to identify the breakdown between the circuitbreaker
contacts and the flashover outside the circuit-breaker,
are presented.
The experimental results show a general tendency to a decrease
in the U, voltage when the temperature is decreased at
constant density (a decrease by about 5% when the temperature
was decreased from +20"C to -25°C). Such a variation would not
have a significant influence in industrial practice. Even if this
variation is very weak, it also appears from the obtained results
that the gas density is not the only parameter which has an influence
on the electric,strength of the gas. However, to compare
results at different temperatures, it would be better to make it at
constant density and not at constant pressure, to avoid the dependency
of the ratio (EJN) on N (where E is the electric
strength and N the density). On the other hand, it seems that the
presence of the liquid in the circuit breaker is not a penalizing
parameter.
The distribution of the electric field corresponding to the
geometrical configuration of the studied circuit-breaker is also
presented.