Title of article :
A new non-communication protection technique for transmission lines
Author/Authors :
Bo، نويسنده , , Z.Q.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 1998
Abstract :
This paper proposes a new non-communication
protection technique for transmission lines. The technique relies
on firstly detection of fault generated high frequency current
transient signals. A specially designed multi-channel filter unit is
then applied to the captured signals to extract desired bands of
high frequency signals. Comparison between the spectral energies
of different bands of the filter outputs determines whether a fault
is internal or external to the protected zone. In addition to the
saving in costs through negating the need for a communication
link, the technique also retains many advantages of the ʹtransient
based protectionʹ technology, such as insensitivity to fault type,
fault position, fault path resistance and fault inception angle. It is
also not affected by CT saturation, the power frequency shortcircuit
level at the terminating busbar or the precise configuration
of the source side networks.
Keywords :
Transmission Line , Non-communication Protection , Transient Based Protection
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY