Title of article
Reducing voltage sags through fault current limitation
Author/Authors
Tosato، نويسنده , , F.، نويسنده , , Quaia، نويسنده , , S.، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2001
Pages
6
From page
12
To page
17
Abstract
Short circuit current limitation in distribution utilities
can be an effective way to improve power quality, since the
expected voltage sag amplitude during faults can be dramatically
reduced.
A simple series LC circuit tuned at the net frequency, with the
capacitor shunted by a metal oxide varistor (MOV), proves to be
a well suited limiter to reach the goal. In the paper, the properties
of such a circuit are analyzed and its operation is investigated
through computer simulation. The relevant pro and con aspects are
outlined and discussed.
Keywords
Fault current limitation , voltagesags. , power quality
Journal title
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year
2001
Journal title
IEEE TRANSACTIONS ON POWER DELIVERY
Record number
400151
Link To Document