• Title of article

    Reducing voltage sags through fault current limitation

  • Author/Authors

    Tosato، نويسنده , , F.، نويسنده , , Quaia، نويسنده , , S.، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2001
  • Pages
    6
  • From page
    12
  • To page
    17
  • Abstract
    Short circuit current limitation in distribution utilities can be an effective way to improve power quality, since the expected voltage sag amplitude during faults can be dramatically reduced. A simple series LC circuit tuned at the net frequency, with the capacitor shunted by a metal oxide varistor (MOV), proves to be a well suited limiter to reach the goal. In the paper, the properties of such a circuit are analyzed and its operation is investigated through computer simulation. The relevant pro and con aspects are outlined and discussed.
  • Keywords
    Fault current limitation , voltagesags. , power quality
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Serial Year
    2001
  • Journal title
    IEEE TRANSACTIONS ON POWER DELIVERY
  • Record number

    400151