Title of article :
Transient behavior of load transformer during subcycle bus transfer
Author/Authors :
Mokhtari، نويسنده , , H.، نويسنده , , Reza Iravani، نويسنده , , M.، نويسنده , , Dewan، نويسنده , , S.B.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2003
Abstract :
Fast (subcycle) bus transfer by means of a static
transfer switch (STS) requires short time intervals for detection
and transfer process. Due to these time intervals, the load
transformer is subjected to a transient process which can be
accompanied by large transient current components through the
transformer. The transient current, in turn, can cause voltage
sag at the load terminal. The STS control logic must be able
to distinguish such a voltage sag from those due to the supply
disturbances and not disconnect the load. This paper provides
simplified analytical expressions to predict F of the load transformer
which can be used to estimate the corresponding voltage
sag. PSCAD/EMTDC-based digital simulation of the actual
nonlinear system is also carried out to substantiate the validity of
the analytical expressions.
Keywords :
sensitive loads , static transfer switch. , Load transformer , power quality
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY