Title of article :
Transient behavior of load transformer during subcycle bus transfer
Author/Authors :
Mokhtari، نويسنده , , H.، نويسنده , , Reza Iravani، نويسنده , , M.، نويسنده , , Dewan، نويسنده , , S.B.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2003
Pages :
8
From page :
1342
To page :
1349
Abstract :
Fast (subcycle) bus transfer by means of a static transfer switch (STS) requires short time intervals for detection and transfer process. Due to these time intervals, the load transformer is subjected to a transient process which can be accompanied by large transient current components through the transformer. The transient current, in turn, can cause voltage sag at the load terminal. The STS control logic must be able to distinguish such a voltage sag from those due to the supply disturbances and not disconnect the load. This paper provides simplified analytical expressions to predict F of the load transformer which can be used to estimate the corresponding voltage sag. PSCAD/EMTDC-based digital simulation of the actual nonlinear system is also carried out to substantiate the validity of the analytical expressions.
Keywords :
sensitive loads , static transfer switch. , Load transformer , power quality
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year :
2003