Title of article :
Compensation of the distortion in the secondary current caused by saturation and remanence in a CT
Author/Authors :
Yong Cheol Kang Ui Jai Lim Sang Hee Kang Crossley، نويسنده , , P.A. ، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2004
Abstract :
Current-transformer (CT) saturation may cause the
maloperation of a protection relay. This is particularly onerous
when the remanent flux in the core of theCTadds to the flux change
caused by the fault. The CT is forced into deep saturation and the
waveshape of the secondary current is severely distorted. An algorithm
for compensating the distortion in the secondary current
caused by saturation and remanence in a CT is described in this
paper.Asecond-difference function detects when theCTfirst starts
to saturate. At this instant, the negative value of the second-difference
function corresponds to the magnetizing current which, in
conjunction with the magnetization curve, is used to estimate the
core flux. This is then used as an initial value to calculate how the
flux changes during the fault. The magnetizing current is estimated
by inserting the estimated core flux into the magnetization curve
and added to the secondary current; the result, the compensated
secondary current, is equal to the secondary referred primary current.
Various test results indicate that the proposed algorithm can
accurately compensate a severely distorted secondary current and
is not affected by remanence. The paper concludes by describing
the hardware implementation of the algorithm on a prototype compensation
unit based on a digital signal processor.
Keywords :
Compensation , current transformer , distortion , second difference. , Saturation , remanent flux
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY
Journal title :
IEEE TRANSACTIONS ON POWER DELIVERY