• Title of article

    A feasibility study of a ventilated beam system in the hot and humid climate: a case-study approach

  • Author/Authors

    Risto Kosonen, P.E، نويسنده , , Freddie Tan، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2005
  • Pages
    10
  • From page
    1164
  • To page
    1173
  • Abstract
    The applications of ventilated beam systems in the hot and humid climate are limited. The main reason is the high risk of condensation. A case-study measurement was conducted in a typical office building in Singapore to investigate the feasibility of a ventilated beam system in the Tropics. The results show that the condensation in the beam system is possible to prevent and to reach dry cooling if infiltration is minimized, supply airflow rate is sufficient to extract humidity of people and tuning of the automation system has conducted probably.
  • Keywords
    Hot and humid climate , Ventilated beams , humidity control , Air–water systems
  • Journal title
    Building and Environment
  • Serial Year
    2005
  • Journal title
    Building and Environment
  • Record number