Title of article
Charge-Voltage curves of surge corona on transmission lines: two measurement methods
Author/Authors
Taku، Noda, نويسنده , , Ono,Takoa، نويسنده , , H، Matsubara, نويسنده , , H.، Motoyama, نويسنده , , S.، Sekioka, نويسنده , , Ametani، A نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2003
Pages
-306
From page
307
To page
0
Abstract
This paper investigates the charge versus voltage (q-v) curves of surge corona on transmission lines. Two measurement methods of the q-v curves are proposed, and field test results are shown to validate the methods. Since the new methods do not require a charge-measuring conductor, such as a corona cage, the q-v curves are measured in the real electric-field distribution. One of the methods obtains the amount of charges q by numerically integrating the digitally stored waveform of injected current, assuming that the line is short in length and open ended. Thus, it is suitable for measurement using an experimental setup. The other calculates q from voltage and current waveforms based on the traveling-wave theory, assuming that the line is long enough to expect no reflected waves, and it is applicable to existing "real" transmission lines. Measured q-v curves are compared with simulated ones, and their physical properties are discussed in the paper
Journal title
IEEE TRANSACTIONS ON POWER DELIVERY
Serial Year
2003
Journal title
IEEE TRANSACTIONS ON POWER DELIVERY
Record number
61607
Link To Document