Underground railway systems, can generate heat from their operations to raise the temperatures of
carriages and the station substantially. This may lead to passenger discomfort and complain especially in warm weather
conditions that prevail in Tehran if underground environment is not cooled. Transportation air conditioning Committee
of American Society of Heating, Refrigerating and air-conditioning Engineers proposed the Relative Warmth Index for
thermal comfort design and investigation in subway environment. In this research, thermal comfort at Tehran metro
stations and carriages of lines 1 and 2 has been studied using this index. The measurements were taken during two
periods of September 2006 and July 2007 at different zones of stations. For this purpose, temperature, relative
humidity and air velocity were measured at different times. The status of the air-conditioning systems together with
passenger traffic was also recorded. A total number of 231 measurements including 114 and 117 measurements were
carried out in September 2006 and in July 2007 respectively. The measurements in September 2006 did not exceed the
thennallimit. However, it did exceed in July 2007. In comparison, with thermal comfort level of metros all over the
world, Tehran Metro stands in an acceptable condition, while the maximum capacity of air-conditioning systems was
not used, if so the thermal comfort condition would be better.