چكيده لاتين :
—Single-phase to earth faults are the most common
faults that occur on transmission lines. As these faults are
temporary in their nature, they can be eliminated by deenergizing
the faulted phase for a short period. This period is
necessary in order for the arc to be extinguished and for the
faulted phase to be reclosed. A special function called autoreclosing
function is included in distance relays to accomplish
this action, i.e. reclosing the open phase at a suitable time. This
paper presents a new adaptive auto-reclosing function by
utilizing a specific feature of the voltage of faulted phase when
the fault is completely eliminated. Using EMTP-RV®, we
precisely simulated secondary arc and different system
conditions to evaluate our proposed method. The simulation
results are promising and show the validity of the proposed
method.